Technical Information
| État de l’article |
Nouveau |
| Nom du fabricant |
KNX sw.act. REG-K/2x/10 w .man.mode |
| Marque |
Schneider Electric
|
| Catégories |
Bus System Devices (KNX/Modbus)
|
| Pays d’origine |
DE |
| Système de bus KNX |
Yes |
| Avec connexion de bus |
Yes |
| Système de bus LON |
No |
| Système de bus KNX radio |
No |
| Fréquence radio bidirectionnelle |
No |
Détails d’emballage
| Niveau d’emballage 1 |
3606485011929 |
| Niveau d’emballage 2 |
3606485011927 |
Autres données techniques
| Méthode de montage |
DRA (adaptateur pour rail DIN) |
| Courant nominal |
10 A |
| Puissance de sortie |
2000 W |
| Tension nominale de fonctionnement |
230 V |
| Système de bus radio fréquent |
No |
| Système de bus Powernet |
No |
| Puissance de commutation max. |
2000 W |
| Nombre max. de contacts de commutation |
2 |
| Nombre d'entrées numériques |
0 |
| Largeur en nombre d'espacements modulaires |
2.5 |
| Courant de commutation max. |
10 A |
| Adapté à la charge C |
Yes |
| Possibilité de connecter différentes phases |
No |
| Opération locale/opération manuelle |
Yes |
| Degré de protection (IP) |
IP20 |
| Avec indication LED |
Yes |
| Possibilité d'extension modulaire |
No |
| Module de bus détachable |
No |
| Profondeur minimale de la boîte d'encastrement |
0 mm |
| Puissance de commutation max. |
0 W |
Description
Switch actuator REG-K/2x230/10 with manual mode. For independent switching of up to 2 loads via make contacts. The function of the switching channels is freely configurable. All switching outlets can be operated manually using push-button operation. Channel status display via LEDs. A green LED indicates readiness for operation. With integrated bus coupler. For installation on DIN rails TH35 according to EN 60715. The bus is connected using a bus connecting terminal. a data rail is not necessary. KNX software functions: Operation as break contact/make contact. Programmable behaviour for download. Delay functions for each channel. Staircase lighting function with/without manual OFF function. Cut-out warning for staircase lighting function. Scenes. Central function. Disable function. Logic operation or priority control. Status feedback function for each channel. Power supply: Nominal voltage: AC 230 V, 50 - 60 Hz. External auxiliary voltage (optional): AC 110 - 240 V, 50 - 60 Hz, max. 2 VA. For each switch output: Nominal current: 10 A, cos Phi 1. 10 A, cos Phi 0.6. Incandescent lamps: AC 230 V, max. 2000 W. Halogen lamps: AC 230 V, max. 1700 W. Fluorescent lamps: AC 230 V, max. 1800 W, uncompensated. AC 230 V, max. 1000 W parallel-compensated. Capacitive load: AC 230 V, max. 105 µF. Device width: 2.5 modules, approx. 45 mm. Contents: With bus connecting terminal and cable cover. Colour: light grey.