| État de l’article | Nouveau |
| Nom du fabricant | RCBO Acti9 iC60 2P 32A C-curve 10kA 30mA A-type |
| Marque | Schneider Electric |
| Catégories |
RCBO - (Earth Leakage Breakers)
|
| Pays d’origine* | PT |
| * The actual country of origin may differ depending on the delivery batch. To confirm the specific country of origin, please contact your account manager. | |
| Code du système harmonisé | 8536 2010 00 |
| Courant nominal | 32 A |
| Tension nominale | 230 V |
| Caractéristique de déclenchement | C |
| Courant de défaut nominal | 0.03 A |
| Type de courant de fuite | A |
| Degré de protection (IP) | IP20 |
| Nombre de pôles protégés | 2 |
| Température ambiante pendant le fonctionnement | -25-40 °C |
| Nombre de pôles (total) | 2 |
| Niveau d’emballage 1 | 3606481157287 |
| Niveau d’emballage 2 | 3606481157284 |
| Niveau d’emballage 3 | 3606481157285 |
| Type de tension | AC |
| Profondeur d'encastrement | 45 mm |
| Tension nominale d'isolation Ui | 500 V |
| Pouvoir de surtension | 0.25 kA |
| Classe de limitation de courant | 3 |
| Catégorie de surtension | 3 |
| Degré de pollution | 2 |
| Largeur en nombre d'espacements modulaires | 2 |
| Fréquence | 50 Hz |
| Conducteur neutre à commutation simultanée | Yes |
| Pouvoir de coupure assigné en cas de court-circuit selon IEC 60947-2 | 15 kA |
| Section du conducteur raccordable à âme pleine | 1-35 mm² |
| Section des conducteurs connectables multi-câblés | 1-25 mm² |
| Avec dispositif de verrouillage | No |
| Installation encastrée | No |
| Version anti-déclenchement de nuisance | No |
| Tension nominale de tenue aux chocs Uimp | 4 kV |
| Pouvoir de coupure assigné en cas de court-circuit Icn selon EN 61009-1 | 0 kA |
| Caractéristique de déconnexion | Non retardée |
| Pouvoir de coupure nominale en cas de court-circuit selon EN 61009 | 0 kA |
This Acti9 iC60 is a modular residual current breaker with overcurrent protection (RCBO). It is a 2P RCBO with 2 protected poles, rated current is 32A, and operating voltage is 220VAC to 240VAC. The earth leakage protection class is A type with a sensitivity of 30mA. The earth-leakage protection time delay is instantaneous. Breaking capacity at 220VAC to 240VAC is 10000A according to EN/IEC 61009-2-1. Breaking capacity at 220VAC to 240VAC is 15kA according to EN/IEC 60947-2. Its unique Visitrip indicator reduces intervention time by showing the faulty circuit. Its Visisafe green strip guarantees the physical opening of the contacts to allow downstream maintenance. Its fast closing mechanism independent of manual operation improves its service life. This product is compliant with EN/IEC 60947-2 and EN/IEC 61009-2-1 standards. Electrical endurance goes up to 10000 cycles, and mechanical endurance goes up to 20000 cycles. The Ue operational voltage is 220VAC to 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 4kV. The frequency is 50Hz. It is DIN rail mountable. The width in 9mm pitches is 4. The product color is white (RAL9003). The dimensions are (W) 36mm x (H) 86mm x (D) 78mm. The weight is 273g. According to IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure. The operating temperature is from -25°C to 40°C. The storage temperature is from -40°C to 70°C.