Register to unlock your exclusive B2B prices and start shopping. Sign up now!

Schneider Electric Motor protection circuit-breakers

Schneider Motor Protection Circuit Breakers selection and coordination

Use these compact, manual motor circuit breakers at the head of each feeder to provide combined short-circuit and overload protection plus a visible isolating function. Typical frames cover 0.1…32 A (small bodies) and up to 63…80 A (larger bodies) with adjustable thermal dials matched to motor FLA. Magnetic trips are fixed or adjustable by frame to clear faults fast (commonly 10–14× In). Breaking capacities are offered for 230/400/690 V networks with Icu choices to suit board fault levels; Ics values preserve service continuity after a fault. Devices carry trip-free mechanisms and lockable handles for LOTO.

Schneider MPCB ranges and frame data

Two practical sizes handle most OEM needs: a 45-mm body for fractional to ~32 A motors and a 55–72-mm body for larger feeders. Dial steps are closely spaced (e.g., 2.5–4–6.3–10–16–25–32 A families) so you can land near nameplate FLA without over-derating. Add-ons include: auxiliary contacts (OF/SD), shunt-trip and undervoltage releases, rotary door handles, phase barriers, and comb busbars that feed rows from a single incomer. Terminal cages accept ferruled fine-strand; torque tables ensure repeatable clamping on warm rails.

Trip characteristics, standards, and thermal behavior

Protection meets IEC/EN 60947-2 (breaking) and 60947-4-1 (motor applications). The inverse-time thermal element follows motor heating; phase-loss sensitivity trips on single-phasing. Magnetic elements clear bolted faults within milliseconds; let-through energy coordinates with contactors and cables. Ambient 40 °C is the reference; apply the manufacturer’s derating for hotter enclosures or group mounting. Terminals are finger-safe IP20; fronts achieve IP40–IP54 inside rated enclosures.

Schneider Motor Starters pairing and coordination

For DOL, reversing, and star-delta feeders, pair the breaker with a coordinated contactor and (where required) an electronic overload relay. Type 1/Type 2 coordination tables define the permitted contactor/short-circuit combination so hardware remains serviceable after a fault. Electronic overloads add trip class selection (10/20/30), ground-fault sensitivity, and unbalance alarms over a dry contact to the PLC. Shunt-trip/UVR on the breaker enables monitored stop: EDM in the safety relay verifies contactor drop-out before restart.

Applications and wiring practices

  • Conveyors, pumps, and fans: one MPCB per motor feeder, line-side comb busbar, auxiliaries back to the PLC for trip diagnostics.

     
  • Drives and soft starters: keep the breaker upstream, sized for the drive input current; short-circuit protection by breaker, thermal by the drive.

     
  • Harsh mains: choose high-Icu frames where MCC fault levels exceed 10–15 kA; use phase barriers on dense rows.
    Use short line/neutral tails, observe creepage from adjacent heat sources, and label the dial setting on the schematic and nameplate for FAT.

     

Interfaces and accessories that cut MTTR

Door-coupled rotary handles provide clear ON/OFF/Tripped position; padlockable OFF secures maintenance. Snap-on OF/SD contacts report state and trip; UVR drops the breaker on control-rail loss. Plug-in motor-starter kits pre-align the breaker above the contactor so you can swap frames without re-drilling. Comb busbars and end-feed blocks reduce copper work and keep phase order uniform cabinet-to-cabinet.

Schneider MPCB Selection criteria for B2B engineers

  1. Network fault level: pick Icu/Ics above calculated kA at the board; check cascading with upstream MCCB.

     
  2. Motor FLA and duty: set the dial to nameplate current; consider service factor and ambient.

     
  3. Starting profile: magnetic pickup must ride through inrush but clear bolted faults quickly; review drive vs across-the-line.

     
  4. Coordination class: apply vendor tables for Type 1/2 with your chosen contactor size.

     
  5. Auxiliaries and control: specify OF/SD, UVR/shunt trip where PLC or safety logic needs positive feedback.
    This is where schneider thermal magnetic breakers fit neatly when one device must both protect and isolate the feeder.

     

System architecture and EMC notes

Place the MPCB directly above the contactor; keep shield bonds short near VFD outputs. Where multiple feeders share one control supply, use undervoltage releases to enforce common drop. Document dial settings, magnetic curve, and auxiliary mappings in the HMI so maintenance can diagnose trips without opening the door.

Applications beyond motors

Use as feeder protection for small transformers, heaters, and brake supplies if the thermal curve matches the load. For DC rails, select DC-rated poles and respect polarity. Where high cycling occurs, check mechanical endurance and consider electronic overloads to keep nuisance trips down.

Advantages of working with Bankoflamps

You get engineered kitting—breaker, contactor, overload, busbar, handles, and auxiliaries matched to your drawings—with project pricing tied to the BOM. The portal shows live EU stock and lead times before you schedule builds, and quotes typically land around the one-hour mark. Ordering by EAN/MPN prevents variant drift; shipment status and downloadable price lists stay in your account. Approved partners can use post-payment up to 30 days. We consolidate partials and lock price-validity windows so phased MCC rollouts stay predictable. Our team checks Icu/Ics, dial range, coordination class, and accessory stacks so cartons arrive rail-ready—no missing links on site.