| Item condition |
New |
| Manufacture name |
RCCB, 4-pole, type B, short-time delayed, In: 63 A, 30 mA |
| Brand |
Siemens
|
| Categories |
RCCB - (Residual Current Breakers)
|
| Country of origin |
DE |
| Harmonized System Code |
8536 2010 00
|
| Rated current |
63 A |
| Rated voltage |
400 V |
| Rated insulation voltage Ui |
0 V |
| Number of poles |
4 |
| Rated fault current |
0.03 A |
| Leakage current type |
B |
| Selective protection |
No |
| Short-circuit breaking capacity (Icw) |
10 kA |
| Surge current capacity |
3 kA |
| Short-time delayed tripping |
Yes |
| Frequency |
50/60 Hz |
| Rated impulse withstand voltage Uimp |
0 kV |
Packing details
| Packing level 1 |
4001869549040 |
Other Technical data
| Mounting method |
DIN rail |
| Built-in depth |
70 mm |
| Pollution degree |
0 |
| Width in number of modular spacings |
4 |
| Explosion-proof |
No |
| Degree of protection (IP) |
IP20 |
| Connectable conductor cross section solid-core |
0.75-35 mm² |
| Connectable conductor cross section multi-wired |
0.75-35 mm² |
| With interlocking device |
Yes |
| Ambient temperature during operating |
-25-45 °C |
| Additional equipment possible |
Yes |
Description
An RCCB is a crucial safety device used to protect people and equipment in an electrical system by detecting earth fault currents. It interrupts the circuit if leakage current exceeds a defined threshold, preventing potential electric shocks or fire hazards.
### Electrical Parameters
Rated current: 63 A. Leakage sensitivity: 30 mA. Short-time delayed operation for improved immunity to transient disturbances. Designed as type B — suitable for detecting both AC and DC residual currents.
### Configuration
4-pole design, compatible with three-phase systems plus neutral. DIN rail mountable, fits standard enclosures. High durability contacts rated for heavy-duty use.
### Approvals/Compatibility
Conforms to IEC 61008-1 standards for residual-current protection devices. Suitable for industrial applications or specialized residential setups where smooth DC or high-frequency AC faults may occur.
#### Technical Notes & Limitations:
- Not suitable for environments subject to extreme temperature variances (e.g., sub-zero temperatures).
- Requires correct installation orientation; ensure line/load connection follows markings on casing.
- Sensitive to harmonics above certain thresholds — consult full technical documentation before choosing this model alongside VFDs or rectifiers.
- Must coordinate with upstream circuit breaker; improper pairing may lead to nuisance tripping during voltage surges from grid fluctuations (test recommended).