| Item condition | New |
| Manufacture name | OVR T2 3L 40-400/690 P SPD T2 3polig 40kA 400/690V |
| Brand | ABB |
| Categories |
Surge Protection Devices (SPD)
|
| Country of origin* | BG |
| * The actual country of origin may differ depending on the delivery batch. To confirm the specific country of origin, please contact your account manager. | |
| Harmonized System Code | 8536 9095 00 |
| Voltage protection level | 2.9 kV |
| Nominal discharge surge current (8/20) | 15 kA |
| Nominal voltage AC | 690 V |
| Voltage protection level L-N | 2.9 kV |
| Degree of protection (IP) | IP20 |
| System configuration DC | No |
| System configuration IT | Yes |
| System configuration TN | Yes |
| System configuration TN-C-S | No |
| Packing level 1 | 3660308515629 |
| Packing level 2 | 3660308515629 |
| Mounting method | DIN rail (top hat rail) 35 mm |
| With remote signalling contact | No |
| Number of conductors (without earthing) | 3 |
| Construction size | 3 modular spacing |
| Max. continuous voltage AC | 760 V |
| Category type 2 | Yes |
| Signalling at the device | Optic |
| Voltage protection level N-PE | 2.9 kV |
| Integrated backup fuse | Yes |
| Max. conductor cross section solid (solid, stranded) | 25 mm² |
| Max. conductor cross section flexible (fine-strand) | 16 mm² |
| System configuration TN-C | Yes |
| System configuration TN-S | No |
| System configuration TT | No |
| System configuration other | No |
| Max. discharge surge current (8/20) | 120 kA |
| Short-circuit breaking capacity (Isccr) | 50 kA |
| Max. overcurrent protection device, series connection (fuse) | 50 A |
| Integrated short-circuit protection | FALSE |
| Integrated short-circuit protection selective to fuse gG | 50 A |
| Leakage-current free | FALSE |