Register to unlock your exclusive B2B prices and start shopping. Sign up now!
OVR T2 2L 40-150 P TS U Surge Protective Device image 1
OVR T2 2L 40-150 P TS U Surge Protective Device image 2
OVR T2 2L 40-150 P TS U Surge Protective Device image 3
OVR T2 2L 40-150 P TS U Surge Protective Device image 4
OVR T2 2L 40-150 P TS U Surge Protective Device thumbnail 1
OVR T2 2L 40-150 P TS U Surge Protective Device thumbnail 2
OVR T2 2L 40-150 P TS U Surge Protective Device thumbnail 3
OVR T2 2L 40-150 P TS U Surge Protective Device thumbnail 4

OVR T2 2L 40-150 P TS U Surge Protective Device

In stock: No Vendor stock: No Minimal order quantity: 1
Price (excl. VAT):
430,26 € per pcs
This price is valid until 31.12.30
EAN: 3660308518613
MPN: 2CTB802343R2100
Package: 1
Box: 5
Estimate delivery time at our warehouse (approx.): By request

Technical Information

Item condition New
Manufacture name OVR T2 2L 40-150 P TS U Surge Protective Device
Brand ABB
Categories Surge Protection Devices (SPD)
Harmonized System Code 8536 3090 00
Voltage protection level 0.6 kV
Nominal discharge surge current (8/20) 20 kA
Nominal voltage AC 240 V
Voltage protection level L-N 0.6 kV
Degree of protection (IP) IP20
System configuration DC No
System configuration IT No
System configuration TN Yes
System configuration TN-C-S Yes

Packing details

Packing level 1 3660308518613
Packing level 2 3660308518613

Other Technical data

Mounting method DIN rail (top hat rail) 35 mm
With remote signalling contact Yes
Number of conductors (without earthing) 2
Construction size 2 modular spacing
Max. continuous voltage AC 240 V
Category type 2 Yes
Signalling at the device Optic
Voltage protection level N-PE 0.6 kV
Integrated backup fuse No
Max. conductor cross section solid (solid, stranded) 25 mm²
Max. conductor cross section flexible (fine-strand) 16 mm²
System configuration TN-C No
System configuration TN-S Yes
System configuration TT No
System configuration other Yes
Max. discharge surge current (8/20) 40 kA
Short-circuit breaking capacity (Isccr) 100 kA
Max. overcurrent protection device, parallel connection (fuse) 0 A
Max. overcurrent protection device, series connection (fuse) 100 A
Integrated short-circuit protection No
Integrated short-circuit protection selective to fuse gG 125 A
Leakage-current free No

Downloads

Description

OVR T2 2L 40 275 P TS U; Přepěťová ochrana; Typ: 2; určeno pro póly: L1,L2; Iimp, Ifi: 40-275; S pomocným kontaktem; S výměnným modulem; dle UL 1449