Technical Information
| Item condition |
New |
| Manufacture name |
OVR SL50 Surge Protective Device |
| Brand |
ABB
|
| Categories |
Surge Protection Devices (SPD)
|
| Harmonized System Code |
8536 3010 00
|
| Max. continuous voltage AC |
56.7 V |
| Nominal discharge surge current (8/20) |
10 kA |
| Nominal load current |
0.75 A |
| Voltage protection level core/core |
90.3 V |
| Voltage protection level core/signal ground |
90.3 V |
| Nominal voltage AC |
50 V |
Packing details
| Packing level 1 |
5415022374988 |
Other Technical data
| Mounting method |
On basic element |
| Connection 1 |
Other |
| Frequency |
45 MHz |
| Lightning impulse current (10/350 µs) |
1.25 kA |
| With remote signalling contact |
No |
| Number of conductors (without earthing) |
0 |
| Limiting frequency |
45 MHz |
| Explosion-tested version |
No |
| Voltage protection level core/earth |
90.3 V |
| Signalling at the device |
None |
| Voltage protection level signal ground/protective ground |
90.3 V |
| Pro-active thermo-control |
No |
| Assembly width |
0 mm |
| Signal disconnection |
No |
Downloads
Description
Die steckbaren Überspannungsschutz Reihenklemmen OVR SL bieten kombinierter Schutz, geprüft in Kategorie D, C, B (gemäß IEC/EN 61643), für verdrillte Doppelleitungen zur Signalübertragung, die entweder einen geringeren Durchgangswiderstand, einen stärkeren Strom und/oder einen höheren Frequenzbereich erfordern. Sie eignen sich für Gleichstromanwendungen bis 750 mA und einer Betriebsspannung von 6 bis 110 Volt. Zur Verwendung an Grenzen von LPZ 0 zum Schutz gegen Überschlag bis LPZ 3, um sensible elektronische Betriebsmittel zu schützen.