| Item condition | New |
| Manufacture name | Surge arrester iPRD40 4P 40kA 350V type 2 |
| Brand | Schneider Electric |
| Categories |
Surge Protection Devices (SPD)
|
| Country of origin* | CN |
| * The actual country of origin may differ depending on the delivery batch. To confirm the specific country of origin, please contact your account manager. | |
| Harmonized System Code | 8536 3030 00 |
| Voltage protection level | 1.6 kV |
| Nominal discharge surge current (8/20) | 15 kA |
| Nominal voltage AC | 350 V |
| Nominal voltage DC | 0 V |
| Voltage protection level L-N | 0 kV |
| Degree of protection (IP) | IP20 |
| Max. PV-voltage | 0 V |
| System configuration DC | No |
| System configuration IT | No |
| System configuration TN | No |
| System configuration TN-C-S | No |
| Packing level 1 | 3606480506376 |
| Packing level 2 | 3606480506373 |
| Packing level 3 | 3606480506374 |
| Mounting method | DIN rail (top hat rail) 35 mm |
| With remote signalling contact | No |
| Number of conductors (without earthing) | 4 |
| Construction size | 4 modular spacing |
| Max. continuous voltage AC | 350 V |
| Category type 2 | Yes |
| Signalling at the device | Optic |
| Max. continuous voltage DC | 0 V |
| Voltage protection level N-PE | 1.4 kV |
| Integrated backup fuse | No |
| Max. conductor cross section solid (solid, stranded) | 25 mm² |
| Max. conductor cross section flexible (fine-strand) | 16 mm² |
| System configuration TN-C | Yes |
| System configuration TN-S | No |
| System configuration TT | No |
| System configuration other | No |
| Max. discharge surge current (8/20) | 40 kA |
| Short-circuit breaking capacity (Isccr) | 50 kA |
| Max. overcurrent protection device, parallel connection (fuse) | 0 A |
| Max. overcurrent protection device, series connection (fuse) | 0 A |
| Integrated short-circuit protection | No |
| Integrated short-circuit protection selective to fuse gG | 0 A |
| Leakage-current free | No |
This Acti9 iPRD surge arrester protects 4P installations. It allows quick replacement of damaged cartridges. This Type 2 device is recommended for high risk level and incoming panel board. It can be turned over to allow the phase/neutral/earth cables to enter through either the top or the bottom. The associated circuit breaker Isc breaking capacity can go up to 50kA. This Acti9 iPRD40 is compatible with TT and TN-S earthing system. The Uc maximum continuous operating voltage in common mode (L/PE or N/PE) is 350VAC. The Up maximum voltage protection level in common mode (L/PE or N/PE) is 1.4kV. The Ue rated operational voltage is 230VAC +/- 10%. The product colour is white (RAL9003).The dimensions are (W) 72mm x (H) 85mm x (D) 69mm. The weight is 416g. The degree of protection is IP20 and IP40 in modular enclosure. The operating temperature is -25°C to 60°C. The storage temperature is -40°C to 85°C. This product is compliant with EN 61643-11 and IEC 61643-11 standards.