Technical Information
| Item condition |
New |
| Manufacture name |
circuit breaker 3VA2 IEC Frame 630 breaking capacity class M Icu=55 kA @ 415 V |
| Brand |
Siemens
|
| Categories |
Power Circuit Breakers
|
| Country of origin |
CZ |
| Harmonized System Code |
8536 2090 00
|
| Rated permanent current Iu |
500 A |
| Number of poles |
4 |
| Rated voltage |
690 V |
| Degree of protection (IP) |
IP40 |
| With switched-off indicator |
No |
| Rated short-circuit breaking capacity lcu at 400 V, 50 Hz |
55 kA |
| Integrated earth fault protection |
Yes |
| Device construction |
Built-in device fixed built-in technique |
Packing details
| Packing level 1 |
4042948827437 |
Other Technical data
| Number of auxiliary contacts as normally open contact |
0 |
| Number of auxiliary contacts as normally closed contact |
0 |
| With integrated under voltage release |
No |
| Overload release current setting |
200-500 A |
| Number of auxiliary contacts as change-over contact |
0 |
| Motor drive integrated |
No |
| Type of control element |
Rocker lever |
| Adjustment range short-term delayed short-circuit release |
300-5000 A |
| Adjustment range undelayed short-circuit release |
750 A |
| Suitable for DIN rail (top hat rail) mounting |
Yes |
| Motor drive optional |
Yes |
| DIN rail (top hat rail) mounting optional |
Yes |
| Complete device with protection unit |
Yes |
Description
circuit breaker 3VA2 IEC frame 630 breaking capacity class M Icu=55kA @ 415V 4-pole, line protection ETU860, LSIG, In=500A overload protection Ir=200A...500A short-circuit protection Isd=0.6..10x In, Ii=1.5..14x In N conductor protection adjustable (OFF, up to 100%) gr.-fault prot., can be sw. off Ig=0.2...1 x In= tg=0.05-0.8s nut keeper kit