| Material core insulation |
Other |
| Core identification |
Colours and numbers |
| Weight |
1600 kg/km |
| Drain wire |
Yes |
| Stranding element |
Pairs |
| Colour outer sheath |
Blue |
| Shape of conductor |
Round |
| Screen over stranding |
Foil |
| Armouring/reinforcement |
None |
| Permitted cable outer temperature during assembling/handling |
-5 °C |
| Permitted cable outer temperature after assembling without vibration |
-40 °C |
| Torsion resistant |
No |
| Number of stranding elements |
2 |
| Screen |
Yes |
| Suspension element |
None |
| Halogen free according to IEC 60754-2 |
No |
| Low smoke according to IEC 61034-2 |
No |
| Outer diameter approx. |
10.2 mm |
| With protective conductor |
No |
| Oil resistant according to IEC 60811-404 |
No |
| Low temperature resistant according to EN 60811-504+505+506 |
No |
| Conductor surface |
Bare |
| Reaction-to-fire according to EN 13501-6: Class |
Eca |
| Reaction-to-fire according to EN 13501-6: Smoke production |
None |
| Reaction-to-fire according to EN 13501-6: Flaming droplets/particles |
None |
| Reaction-to-fire according to EN 13501-6: Acidity |
None |
| Min. permitted bending radius, moving application/free movement |
153 mm |
| Min. permitted bending radius, stationary application/permanent installation |
76.5 mm |
| Specification core insulation |
Polyethylene (PE) |
| Cable geometry |
Round |
| Conductor resistance at 20 °C |
39.2 Ohm/km |
| Core identification according to HD 308 S2 |
No |
| Flame retardant according to IEC 60332-1-2 |
Yes |
| Flame retardant according to IEC 60332-3-21 (Cat A F/R) |
No |
| Flame retardant according to IEC 60332-3-22 (Cat A) |
No |
| Flame retardant according to IEC 60332-3-23 (Cat B) |
No |
| Flame retardant according to IEC 60332-3-24 (Cat C) |
No |
| Flame retardant according to IEC 60332-3-25 (Cat D) |
No |
| Halogen free according to IEC 60754-1 |
No |
| Halogen free according to IEC 60754-3 |
No |