Technical Information
| Item condition |
New |
| Manufacture name |
Undervoltage release (MN), TeSys Deca, 220-240 V AC 50 Hz, safety device for use with GV2ME |
| Brand |
Schneider Electric
|
| Categories |
Trip & Release Units
|
| Country of origin |
CZ |
| Harmonized System Code |
8536 5080 00
|
| Type of electric connection |
Screw connection |
| Rated control supply voltage at AC 50 Hz |
220-240 V |
| Voltage type for actuating |
AC |
Packing details
| Packing level 1 |
3389110346107 |
| Packing level 2 |
3389110346105 |
Other Technical data
| Delayed |
No |
| Suitable for off-load switch |
No |
| Suitable for overload relay |
No |
| Suitable for motor safety switch |
Yes |
| Suitable for power circuit breaker |
Yes |
| Number of contacts as normally closed contact |
0 |
| Number of contacts as normally open contact |
0 |
| Number of contacts as change-over contact |
0 |
Downloads
Description
TeSys GV electrical trip, MN undervoltage release, 220-240V AC 50Hz, for motor circuit breakers GV2ME used in safety-related systems. It trips the circuit breaker when the control voltage drops below 0.35 Uc, possible opening between 0.35-0.7 Uc. Closing of the circuit breaker is only possible when the control voltage is applied in the range 0.85-1.1 Uc. To be mounted on right-hand side of the circuit breaker, connection by screw clamp terminals. Multi standards certified (IEC, UL, CSA, CCC, EAC, INRS, VDE 0113), Green Premium compliant (RoHS/REACh).