Technical Information

Item condition New
Manufacture name Type 2+3 surge arrester DEHNcord 3-phase for electr. inst. systems
Brand Dehn
Categories Surge Protection Devices (SPD)
Country of origin CN
Harmonized System Code 8536 3030 00
Nominal discharge surge current (8/20) 10 kA
Nominal voltage AC 230 V
Voltage protection level L-N 1.5 kV
Degree of protection (IP) IP20

Packing details

Packing level 1 4013364436053, 4013364436053

Other Technical data

Mounting method DIN rail (top hat rail) 35 mm
With remote signalling contact Yes
Number of conductors (without earthing) 4
Max. continuous voltage AC 275 V
Category type 2 Yes
Signalling at the device Optic
Max. continuous voltage DC 350 V
Voltage protection level N-PE 1.5 kV
Max. conductor cross section solid (solid, stranded) 6 mm²
Max. conductor cross section flexible (fine-strand) 6 mm²
System configuration TN-S Yes
System configuration TT Yes
Max. discharge surge current (8/20) 20 kA
Short-circuit breaking capacity (Isccr) 6 kA
Max. overcurrent protection device, parallel connection (fuse) 40 A
Max. overcurrent protection device, series connection (fuse) 25 A

Downloads

Description

Three-phase DEHNcord type 2 + type 3 surge arrester according to EN 61643-11 with a compact design for all installation systems; mounted on DIN rails or, in confined spaces, using screw lugs. For installation in conformity with the lightning protection zone concept at the boundaries from 0B – 1 and higher.