Technical Information
Item condition |
New |
Manufacture name |
trip unit MicroLogic 5.3 A-Z for ComPact NSX 630 circuit breakers, electronic, rating 630 A, 3 poles 3d |
Brand |
Schneider Electric
|
Categories |
Trip & Release Units
|
Rated permanent current Iu |
630 A |
Number of poles |
3 |
Short-circuit release function |
Delayed |
Overload release current setting |
263-756 A |
Type of motor protection |
Electronic release |
Packing details
Packing level 1 |
3606480021879 |
Packing level 2 |
3606480021877 |
Other Technical data
With ground fault protection function |
No |
Initial value of the undelayed short-circuit release - setting range |
945 A |
End value adjustment range undelayed short-circuit release |
6930 A |
Voltage type for actuating |
Self powered |
Downloads
Description
This Micrologic 5.3 A-Z is a 3 poles 3d electronic trip unit used on Compact NSX 630 circuit breakers. This 630A rating electronic trip unit is used on specific 16 Hz 2/3 distribution systems for railroad applications. It embeds adjustable long time protection against overloads. It provides also adjustable short-time protection and instantaneous protection against short-circuits. Micrologic 5.3 A-Z indicates overloads with Alarm LEDs. The green Ready LED flashes if the circuit breaker is ready to trip. Micrologic 5.3 A-Z is equipped with a display module that gives current measurement and allows fine adjustment settings. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and Compact NSX basic frame.