Technical Information
| Item condition |
New |
| Manufacture name |
trip unit MicroLogic 5.0 A, ComPact NS630b to NS3200 fixed, selective protections |
| Brand |
Schneider Electric
|
| Categories |
Trip & Release Units
|
| Rated permanent current Iu |
630 A |
| Number of poles |
0 |
| Short-circuit release function |
Delayed |
| Overload release current setting |
252-3200 A |
| Type of motor protection |
Electronic release |
Packing details
| Packing level 1 |
3303430335122 |
Other Technical data
| Rated control supply voltage at DC |
24 V |
| With ground fault protection function |
No |
| Initial value of the undelayed short-circuit release - setting range |
1260 A |
| End value adjustment range undelayed short-circuit release |
48000 A |
| Voltage type for actuating |
Self powered |
Downloads
Description
Micrologic 5.0A (Ammeter) is an electronic trip unit used on Compact NS630b to NS3200 circuit breakers. This control unit has a selective protection and is designed to protect power circuits and loads. It embeds adjustable long time protection against overloads. It provides also adjustable short-time protection and instantaneous protection against short-circuits. Micrologic 5.0A indicates overloads with an Alarm LED. It is able to display the trip cause through 3 others LEDs. Micrologic 5.0A is equipped with a digital LCD screen that displays the true RMS current values with 1.5% accuracy. This trip unit can be associated with Compact NS basic frame.