Technical Information
| Item condition |
New |
| Manufacture name |
PKZM0-1,6-T-PI Transformer-protective circuit-breaker, 1 - 1.6 A, Push in terminals |
| Brand |
EATON
|
| Categories |
Power Circuit Breakers
|
| Country of origin* |
DE |
|
* The actual country of origin may differ depending on the delivery batch.
To confirm the specific country of origin, please contact your account manager.
|
| Harmonized System Code |
8536 2010 00
|
| Rated permanent current Iu |
1.6 A |
| Number of poles |
3 |
| Rated voltage |
690 V |
| Degree of protection (IP) |
IP20 |
| With switched-off indicator |
No |
| Rated short-circuit breaking capacity lcu at 400 V, 50 Hz |
150 kA |
| Integrated earth fault protection |
No |
| Device construction |
Built-in device fixed built-in technique |
Packing details
| Packing level 1 |
4015081972524 |
Other Technical data
| Number of auxiliary contacts as normally open contact |
0 |
| Number of auxiliary contacts as normally closed contact |
0 |
| With integrated under voltage release |
No |
| Overload release current setting |
1.6 A |
| Number of auxiliary contacts as change-over contact |
0 |
| Position of connection for main current circuit |
Other |
| Motor drive integrated |
No |
| Type of electrical connection of main circuit |
Spring clamp connection |
| Type of control element |
Turn button |
| Adjustment range short-term delayed short-circuit release |
0 A |
| Adjustment range undelayed short-circuit release |
32 A |
| Suitable for DIN rail (top hat rail) mounting |
No |
| Motor drive optional |
No |
| DIN rail (top hat rail) mounting optional |
Yes |
| Complete device with protection unit |
No |
Description
Transformer-protective circuit-breaker, IEC/EN 60947, VDE 0660, Overload releases 1 - 1.6 A: max. 32 A, Rated permanent current Iu 1.6 A, Type of control element Turn button, Number of poles 3, Device IP20, Terminations IP20, Storage - 40 - 80 °C, Open -25 - +55 °C, Direction of incoming supply as required