Technical Information
| Item condition |
New |
| Manufacture name |
Transformer, 1-ph. PN/PN(kVA)2/11.5, Upri=400-230 V +/-15, Usec(V) 2x115 |
| Brand |
Siemens
|
| Categories |
Low Voltage Transformers
|
| Country of origin* |
CZ |
|
* The actual country of origin may differ depending on the delivery batch.
To confirm the specific country of origin, please contact your account manager.
|
| Harmonized System Code |
8504 3180 00
|
| Width |
176 mm |
| Height |
164 mm |
| Depth |
158 mm |
| Conductor material |
Other |
| Primary voltage 1 |
415 V |
| Primary voltage 2 |
400 V |
| Primary voltage 3 |
385 V |
| Built as safety transformer |
No |
| Built as isolating transformer |
No |
| Primary voltage 4 |
245 V |
| Primary voltage 5 |
230 V |
| Primary voltage 6 |
215 V |
| Secondary voltage 1 |
230 V |
| Secondary voltage 2 |
115 V |
| Rated apparent power |
2000 VA |
Packing details
| Packing level 1 |
4001869902807 |
Other Technical data
| Modular version |
No |
| Suitable for mounting on PCB |
No |
| Ring core |
No |
| Built as energy saving transformer |
No |
| Type of insulation material according to IEC 85 |
B |
| Short-circuit-proof |
No |
| Relative short circuit voltage |
1.9 % |
Description
SITAS transformer; phases: 1; PN/PN(S6)(KVA):2 / 9.7; UPRI(V): 400-230+/-15; Usec(V):2x115; Isec(A):2x8.7; F(HZ):50...60; Vector gr./shield wng.:II0 /0; TA/ISO Cl:40 /B; IP00; Connection: screw/tab connection; mounting: screws; EN 61558-2-1, -2-2, -2-4 UL/CSA-recognized >Control transformer >Isolating transformer The 4AM transformers unite all properties of single-phase safety, isolating, control and line transformers. With these properties, they can effortlessly handle any application. The control transformers are also characterized by their short-time rating.