Technical Information
| Item condition |
New |
| Manufacture name |
Surge protection module for earthed outlets |
| Brand |
Dehn
|
| Categories |
Surge Protection Devices (SPD)
|
| Country of origin |
DE |
| Harmonized System Code |
8536 3010 00
|
| Max. continuous voltage AC |
255 V |
| Total discharge current (8/20) (L+N-PE) |
5 kA |
| Nominal discharge surge current (8/20) (L-N) |
3 kA |
| Nominal voltage AC |
230 V |
| Voltage protection level L-N |
1.25 kV |
| Voltage protection level L-PE/N-PE |
1.5 kV |
| Degree of protection (IP) |
IP20 |
Packing details
| Packing level 1 |
4013364076709, 4013364076709 |
Other Technical data
| Mounting method |
Wall socket |
| Number of poles |
2 |
| Category type 3 |
Yes |
| Signalling at the device |
Acoustic |
| Max. overcurrent protection device, parallel connection (fuse) |
16 A |
| Max. overcurrent protection device, series connection (fuse) |
16 A |
Downloads
Description
Two-pole STC-Modul surge arrester (type 3 according to EN 61643-11) with monitoring device and disconnector. Enhanced safety du to Y protective circuit. For protecting electronic equipment against surges. For installation in combination with standard earthed socket outlets. For installation in conformity with the lightning protection zone concept at the boundaries from 1 – 2 and higher.