Technical Information
| Item condition |
New |
| Manufacture name |
S811+V72V3S Soft starter, 720 A, 200 - 690 V AC, Us= 24 V DC, with control unit and pump algorithm, for 690-V grids, Frame size V |
| Brand |
EATON
|
| Categories |
Soft Starters
|
| Country of origin* |
DO |
|
* The actual country of origin may differ depending on the delivery batch.
To confirm the specific country of origin, please contact your account manager.
|
| Rated operating voltage Ue |
200-690 V |
| Rated operation current Ie at 40 °C Tu |
720 A |
| Rated power three-phase motor, inline, at 230 V |
200 kW |
| Rated surrounding temperature without derating |
50 °C |
Packing details
| Packing level 1 |
4015081655014 |
Other Technical data
| Function |
Single direction |
| With display |
Yes |
| Rated control supply voltage at AC 50 Hz |
0 V |
| Rated control supply voltage at AC 60 Hz |
0 V |
| Rated control supply voltage at DC |
24 V |
| Degree of protection (IP) |
IP20 |
| Release class |
Adjustable |
| Rated power three-phase motor, inline, at 400 V |
400 kW |
| Rated power three-phase motor, inside delta, at 230 V |
200 kW |
| Rated power three-phase motor, inside delta, at 400 V |
630 kW |
| Integrated motor overload protection |
Yes |
| Voltage type for actuating |
DC |
| Internal bypass |
Yes |
| Torque control |
No |
| Degree of protection (NEMA) |
Other |
Description
Soft starter, Description: With internal bypass contacts, Function: Soft starter for three-phase loads, with control unit and pump algorithm, for 690-V grids, Mains supply voltage (50/60 Hz): ULN= 200 - 690 V AC, Supply voltage: Us= 24 V DC, Control voltage: UC= 24 V DC, Assigned motor rating (Standard connection, In-Line) at 400 V, 50 Hz: P= 400 kW, at 690 V, 50 Hz: P= 630 kW, at 460 V, 60 Hz: P= 600 HP, Rated operational current AC-53: Ie= 720 A, Startup class: CLASS 10 (star-delta replacement), CLASS 20 (heavy starting duty 3 x Ie for 45 s), CLASS 30 (6 x Ie for 30 s), Rated operational voltage: Ue= 200 V, 230 V, 400 V, 480 V, 600 V , 690 V, Connection to SmartWire-DT: no, Frame size: V, Ordering information: Terminal blocks for the terminals are required for frame sizes T, U, and V -> Accessories, Standards: IEC/EN 60947-4-2, UL 508, CSA22.2-14-1995, GB14048