Technical Information
| Item condition |
New |
| Manufacture name |
Residual current circuit-breaker, all-current sensitive, 125 A, 4p, 500 mA, type S/BFQ |
| Brand |
EATON
|
| Categories |
RCCB - (Residual Current Breakers)
|
| Country of origin |
DE |
| Harmonized System Code |
8536 3030 00
|
| Mounting method |
DIN rail |
| Rated current |
125 A |
| Rated voltage |
415 V |
| Number of poles |
4 |
| Rated fault current |
0.5 A |
| Leakage current type |
B |
| Degree of protection (IP) |
IP20 |
Packing details
| Packing level 1 |
4015081676750 |
| Packing level 2 |
9008790537608 |
Other Technical data
| Voltage type |
AC |
| Built-in depth |
70.5 mm |
| Rated insulation voltage Ui |
440 V |
| Selective protection |
Yes |
| Short-circuit breaking capacity (Icw) |
10 kA |
| Surge current capacity |
5 kA |
| Pollution degree |
2 |
| Width in number of modular spacings |
4 |
| Short-time delayed tripping |
No |
| Explosion-proof |
No |
| Frequency |
50 Hz |
| Connectable conductor cross section solid-core |
1.5-50 mm² |
| Connectable conductor cross section multi-wired |
1.5-16 mm² |
| With interlocking device |
Yes |
| Ambient temperature during operating |
-25-60 °C |
| Additional equipment possible |
Yes |
| Rated impulse withstand voltage Uimp |
4 kV |
Description
Residual current circuit-breaker FRCmM-125, 4 pole, Rated current In: 125 A, Rated short-circuit strength Icn: 10 with back-up fuse kA, Rated fault current IΔN: 0.5 A, Residual current circuit-breaker - frequency converter-proof