Register to unlock your exclusive B2B prices and start shopping. Sign up now!
PFL6-16/1N/B/003 RCD/MCB combination, 16 A, 30 mA, MCB trip characteristic: B, 1p+N, RCD trip characteristic: AC image 1

PFL6-16/1N/B/003 RCD/MCB combination, 16 A, 30 mA, MCB trip characteristic: B, 1p+N, RCD trip characteristic: AC

In stock In vendor's stock
Price (excl. VAT):
24,65 €
This price is valid until 31.12.25 or while stock lasts
EAN: 4015082864316
MPN: 286431
Package: 1
Box: 60
Estimate delivery time at our warehouse (approx.): 1-4 weeks

Technical Information

Item condition New
Manufacture name PFL6-16/1N/B/003 RCD/MCB combination, 16 A, 30 mA, MCB trip characteristic: B, 1p+N, RCD trip characteristic: AC
Brand EATON
Categories RCBO - (Earth Leakage Breakers)
Country of origin* RO
* The actual country of origin may differ depending on the delivery batch. To confirm the specific country of origin, please contact your account manager.
Harmonized System Code 8536 3030 00
Rated current 16 A
Rated voltage 230 V
Release characteristic B
Rated fault current 0.03 A
Leakage current type AC
Degree of protection (IP) IP20
Number of protected poles 1
Ambient temperature during operating -25-40 °C
Number of poles (total) 2

Packing details

Packing level 1 4015082864316
Packing level 2 9007912536956, 9007912536956

Other Technical data

Voltage type AC
Built-in depth 69.5 mm
Rated insulation voltage Ui 440 V
Surge current capacity 0.25 kA
Current limiting class 3
Over voltage category 3
Pollution degree 2
Width in number of modular spacings 2
Frequency 50 Hz
Concurrently switching neutral conductor Yes
Rated short-circuit breaking capacity according to IEC 60947-2 0 kA
Connectable conductor cross section solid-core 1-25 mm²
Connectable conductor cross section multi-wired 1-25 mm²
With interlocking device No
Flush-mounted installation No
Anti-nuisance tripping version No
Rated impulse withstand voltage Uimp 4 kV
Rated short-circuit breaking capacity Icn according to EN 61009-1 6 kA
Disconnection characteristic Undelayed
Rated short-circuit breaking capacity according to EN 61009 6 kA

Description

RCBO (residual-current circuit breaker with overload protection) PFL6, 1 pole+N, Rated current In: 16 A, Rated fault current IΔN: 0.03 A, Rated switching capacity according to IEC/EN 61009: 6 kA, Switchgear for residential and commercial applications