Technical Information
Item condition |
New |
Manufacture name |
MR-F-CI4 Modbus RTU |
Brand |
METZ CONNECT
|
Categories |
Bus System Devices (KNX/Modbus)
|
Country of origin |
DE |
Harmonized System Code |
8517 6200 00
|
Bus system KNX |
No |
Bus system radio frequent |
No |
Bus system Powernet |
No |
With bus connection |
Yes |
Other bus systems |
Other |
Bus system LON |
No |
Bus system KNX radio |
No |
Packing details
Packing level 1 |
4251394620756, 4251394620756 |
Other Technical data
Mounting method |
DRA (DIN-rail adapter) |
Model |
Base module |
Number of inputs |
4 |
Input current drive |
Yes |
Input voltage drive |
Yes |
Width in number of modular spacings |
2 |
Degree of protection (IP) |
IP20 |
With LED indication |
Yes |
Min. depth of built-in installation box |
60 mm |
Description
The Modbus module with 4 analog inputs was developed for decentralized switching tasks. It is suitable for detecting currents and voltages of, for example, active temperature sensors, electrical vent and mixing valves, valve positions, etc. Each input can be set as current or voltage input by DIP switches on the front. The inputs can be scanned with standard registers via a Modbus master. The module address, the baud rate and the parity are set with 2 rotary switches on the front or by software. Suitable for decentralized mounting on TH35 rails according to IEC 60715 in electrical distribution cabinets.Connection with spring clamp terminal blocks (push-in)