| Item condition | New |
| Manufacture name | MCB Acti9 C120H 2P 63A C 15kA |
| Brand | Schneider Electric |
| Categories |
Circuit breakers 63A
|
| Country of origin* | FR |
| * The actual country of origin may differ depending on the delivery batch. To confirm the specific country of origin, please contact your account manager. | |
| Harmonized System Code | 8536 2010 00 |
| Rated current | 63 A |
| Rated voltage | 415 V |
| Release characteristic | C |
| Width in number of modular spacings | 3 |
| Number of poles (total) | 2 |
| Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V | 15 kA |
| Packing level 1 | 3606480380273 |
| Packing level 2 | 3606480380270 |
| Packing level 3 | 3606480380271 |
| Voltage type | AC |
| Built-in depth | 44 mm |
| Frequency | 50-60 Hz |
| Rated insulation voltage Ui | 500 V |
| Current limiting class | 3 |
| Over voltage category | 4 |
| Pollution degree | 3 |
| Explosion-proof | No |
| Degree of protection (IP) | IP20 |
| Number of protected poles | 2 |
| Concurrently switching neutral conductor | Yes |
| Connectable conductor cross section solid-core | 1.5-50 mm² |
| Connectable conductor cross section multi-wired | 1-35 mm² |
| Ambient temperature during operating | -30-60 °C |
| Flush-mounted installation | No |
| Additional equipment possible | Yes |
| Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V | 15 kA |
| Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V | 30 kA |
| Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V | 15 kA |
| Rated impulse withstand voltage Uimp | 6 kV |
This Acti9 C120H is a low voltage multistandard miniature circuit breaker (MCB). It is a 2P circuit breaker with 2 protected poles, 63A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 15000A at 230VAC to 400VAC conforming to EN/IEC 60898-1 standard and 15000A at 230VAC to 400VAC conforming to EN/IEC 60898-1 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. This miniature circuit breaker combines functions of circuit protection against short circuit and overload current, control and isolation. The presence of green strip guarantees that contacts open physically and allows work to be carried out safely on the downstream circuit. Its fast closing mechanism improves its service life. Acti9 C120 offer is dedicated to industrial and tertiary buildings. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is going from 380VAC to 415VAC. The Ui rated insulation voltage is 500VAC. Its limitation class 3 (according to EN/IEC60898-1) improves downstream circuit protection cost. The product can be clipped on a DIN rail. Its width is 6 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is white (RAL9003). The dimensions are (W) 54mm x (H) 81mm x (D) 73mm. The weight is 0.41kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 60°C. The storage temperature is -40°C to 70°C.