Technical Information
                
                    
                        
                            | Item condition | New | 
                        
                            | Manufacture name | Contactor, 24 V DC, 3 pole, 380 V 400 V, 5.5 kW, Contacts N/C = Normally closed= 1 NC, Screw terminals, DC operation | 
                                                    
                                | Brand | EATON | 
                                                                            
                                | Categories | AC Power Contactors 
 | 
                                                                            
                                | Country of origin | DE | 
                                                                            
                                | Harmonized System Code | 8536 4900 00 | 
                                                                                                                                    
                                    | Rated operation power at AC-3, 400 V | 5.5 kW | 
                                                            
                                    | Number of normally open contacts as main contact | 3 | 
                                                            
                                    | Number of normally closed contacts as main contact | 0 | 
                                                            
                                    | Rated operation current Ie at AC-3, 400 V | 12 A | 
                                                            
                                    | Rated control supply voltage at AC 50 Hz | 0 V | 
                                                            
                                    | Rated control supply voltage at AC 60 Hz | 0 V | 
                                                            
                                    | Rated control supply voltage at DC | 24 V | 
                                                            
                                    | Type of electrical connection of main circuit | Screw connection | 
                                                            
                                    | Voltage type for actuating | DC | 
                                                                        
                 
                                    Packing details
                    
                        
                                                            
                                    | Packing level 1 | 4015081879861 | 
                                                    
                     
                
                                    Other Technical data
                    
                                                    
                                                                    
                                        | Modular version | No | 
                                                                    
                                        | Number of auxiliary contacts as normally open contact | 0 | 
                                                                    
                                        | Number of auxiliary contacts as normally closed contact | 1 | 
                                                                    
                                        | Rated operation current Ie at AC-1, 400 V | 22 A | 
                                                                    
                                        | Rated operation current Ie at AC-4, 400 V | 6.6 A | 
                                                                    
                                        | Rated operation power at AC-4, 400 V | 3 kW | 
                                                                    
                                        | Rated operation power NEMA | 3.7 kW | 
                                                            
                                             
                
                
                
                
                
                                    Description
                    
                        Contactor, Application: Contactors for Motors, Mini Contactors for Motors and Resistive Loads, DILEM contactors, Utilization category: AC-1: Non-inductive or slightly inductive loads, resistance furnaces, NAC-3: Normal AC induction motors: starting, switch off during running, AC-4: Normal AC induction motors: starting, plugging, reversing, inching, Connection technique: Screw terminals, Description: With auxiliary contact, Number of poles: 3 pole, Rated operational current AC-3 380 V 400 V: Ie= 12 A, Rated operational current AC-1 Conventional free air thermal current, 3 pole, 50 - 60 Hz Open at 40 °C: Ith =Ie= 22 A, enclosed: Ith= 16 A , Rated operational current AC-1 Conventional free air thermal current, 1 pole open: Ith= 50 A, enclosed: Ith= 40 A, Max. rating for three-phase motors, 50 - 60 Hz AC-3 220 V 230 V: P= 3 kW, 380 V 400 V: P= 5.5 kW, 660 V 690 V: P= 4 kW, Max. rating for three-phase motors, 50 - 60 Hz AC-4 220 V 230 V: P= 1.5 kW, 380 V 400 V: P= 3 kW, 660 V 690 V: P= 3 kW, For use with: …DILE, Contacts N/C = Normally closed: 1 NC, Voltage AC/DC: DC operation