Rated short-circuit breaking capacity lcu at 400 V, AC
50 kA
Adjustment range undelayed short-circuit release
1120 A
Phase failure sensitive
Yes
Device construction
Complete device in housing
Packing details
Packing level 1
3606481304520
Description
TeSys GV motor circuit breaker, 3 poles (3P), 73A/690V, for 3-phase motor applications 37kW@400V. It provides a magnetic protection with a tripping level at 15xIn, high breaking capacity Icu 50kA@400V. Connection by Everlink BTR screw terminals. Start-stop control by rotary handle guaranteed for 20 000 cycles AC-3. To complete motor protection, use it in association with a thermal overload relay LRD380 (to be ordered separately). Multi standards certified (IEC, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).