Line separator
In stock: No
Vendor stock: No
Minimal order quantity: 1
Price (excl. VAT):
127,13 €
This price is valid until 24.12.25
Estimate delivery time at our warehouse (approx.):
4-6 weeks
Technical Information
Item condition |
New |
Manufacture name |
Line separator |
Brand |
Siemens
|
Categories |
Intruder Alarm Systems
|
Country of origin |
CN |
Harmonized System Code |
8536 3010 00
|
Type of accessory/spare part |
Address card |
Material |
Plastic |
Accessory |
No |
Spare part |
No |
Packing details
Packing level 1 |
4047625014940 |
Description
To avoid the breakdown of several stub lines in case of a short-circuit, line separators may be inserted. The line separator is used where several stub lines are connected to the FDnet/C-NET at one point, if no other device is given between the T-tap. For retrofitting of existing, collective systems to addressable Sinteso/Cerberus PRO fire detection systems. The line separator is an electronic switch, integrated into the FDnet/C-NET. It separates the negative conductor in case of a short-circuit, so that the short-circuit-free side can continue to operate. The line separator has 2x2 connectors for the detector line. Yellow LED for the status indication signals the short-circuit separation.