Technical Information
| Toote seisukord |
Uus |
| Tootja nimi |
VZ208C Zone Valve, 2-Way, PN16, DN15, 15 mm O/D Compression, Kvs 0.6 m³/h, M30 Actuator Connection, 2.5 mm Stroke, Stem Up Closed |
| Bränd |
Schneider Electric
|
| Kategooriad |
Control Valves and Actuators
|
| Päritoluriik* |
IT |
|
* The actual country of origin may differ depending on the delivery batch.
To confirm the specific country of origin, please contact your account manager.
|
| Pinnatöötlus |
Muul viisil |
| Juhtsignaal |
Kahepunktiline |
| Materjal |
Muul viisil |
| Toote surveklass |
PN 16 |
| Ääriku surveklass |
PN 16 |
| Ühendused |
Surverõngas |
| Suurim diferentsiaalrõhk avatud asendis |
0 bar |
| Kvs väärtuse lekkekadu |
0 % |
| Juhtimissuhe (Svo) |
50 % |
| Pinnase omadused |
Võrdne osakaal |
| Sulgemisrõhk |
0 bar |
Pakendamise üksikasjad
| Pakkimistase 1 |
3606481518217 |
Muud tehnilised andmed
| Laius |
0 mm |
| Kõrgus |
0 mm |
| Sügavus |
0 mm |
| Suurim pidev ümbrustemperatuur |
95 °C |
| Minimaalne ümbrustemperatuur (pidev) |
5 °C |
| Kõigi ühenduste toru välisläbimõõt |
15 mm |
| Ühenduse 1 pikkus |
0 mm |
| Ühenduse 2 pikkus |
0 mm |
| Ühenduse 1 tööpikkus |
0 mm |
| Ühenduse 2 tööpikkus |
0 mm |
| Talitlusaeg |
0 s |
| Koos ühenduse 1 liitmikuga |
Yes |
| Koos ühenduse 2 liitmikuga |
Yes |
| Kere materjal |
Messing |
| Kvs väärtus |
0.6 |
| Otskontaktidega |
No |
| Suurim elektriline sisendvõimsus |
0 VA |
| Nimi-siseläbimõõt |
1/2 tolli (15) |
| Abikontaktid |
No |
Allalaadimised
Kirjeldus
The VZ28 is a short stroke and small linear zone valve designed for control of hot and chilled water. The valve is used with a thermo-electric actuators type MZ14. The valves utilise a double O-ring design on the plug to ensure a leak tight seal on both valve ports, this ensures no loss of energy leakage through the valve. 15mm Compression connection DN15, Kvs: .6 m³/h Two-way valve, Normally closed without actuator fitted. Pressure class PN16, stroke 2.5 mm. It is recommended to fit a strainer upstream of the valve to increase reliability and to follow water treatment guidelines as detailed in VDI 235. Valves should be installed in the return pipe to reduce exposure to media temperature extremes.