Technical Information
| Item condition |
New |
| Manufacture name |
EB2 250/4E 160A 4p |
| Brand |
ETI
|
| Categories |
Power Circuit Breakers
|
| Rated permanent current Iu |
160 A |
| Number of poles |
4 |
| Degree of protection (IP) |
IP20 |
| With switched-off indicator |
Yes |
| Rated short-circuit breaking capacity lcu at 400 V, 50 Hz |
70 kA |
| Integrated earth fault protection |
No |
| Device construction |
Built-in device fixed built-in technique |
Packing details
| Packing level 1 |
3838895413660, 3838895413660, 3838895413660, 3838895413660 |
| Packing level 2 |
3838895413660, 3838895413660 |
Other Technical data
| Overload release current setting |
64-160 A |
| Motor drive integrated |
No |
| Type of electrical connection of main circuit |
Screw connection |
| Type of control element |
Rocker lever |
| Adjustment range short-term delayed short-circuit release |
160-1600 A |
| Adjustment range undelayed short-circuit release |
896-1600 A |
| Suitable for DIN rail (top hat rail) mounting |
No |
| Motor drive optional |
Yes |
| DIN rail (top hat rail) mounting optional |
No |
| Complete device with protection unit |
No |
Description
Molded Case Circuit Breaker, EB2 250/4E 160A 4p, Release system - thermal/magnetic 0,4-1/ADJUST, Frame size 250A, Rated current (A) 160, Short circuit capacity (kA) 70/70, Function Low voltage moulded case circuit breakers, No. Of poles 4