Technical Information
| Item condition |
New |
| Manufacture name |
DEHNrapid lightn. curr. arr. LSA f. 10 pairs, fail-safe funct., fault |
| Brand |
Dehn
|
| Categories |
Surge Protection Devices (SPD)
|
| Country of origin* |
DE |
|
* The actual country of origin may differ depending on the delivery batch.
To confirm the specific country of origin, please contact your account manager.
|
| Harmonized System Code |
8536 3010 00
|
| Mounting method |
LSA-plus plug-in |
| Signalling at the device |
Optic |
Packing details
| Packing level 1 |
4013364107564, 4013364107564 |
Other Technical data
| Lightning impulse current (10/350 µs) |
5 kA |
| Max. continuous voltage AC |
127 V |
| Nominal discharge surge current (8/20) |
10 kA |
| Nominal load current |
0.4 A |
| Nominal voltage DC |
180 V |
| Voltage protection level core/core |
500 V |
| Voltage protection level core/earth |
450 V |
| Max. continuous voltage DC |
180 V |
Downloads
Description
Lightning current carrying DRL plug-in SPD block (10 pairs) for almost all applications. Expandable to a combined lightning current and surge arrester by means of a DRL protective plug. The integrated disconnection block contacts allow testing, measuring and patching with plugged-in protection. The three-pole gas discharge tubes have a fail-safe function with visual fault indicator.