Technical Information
| Item condition |
New |
| Manufacture name |
DEHNbloc H 3 lightning current arrester |
| Brand |
Dehn
|
| Country of origin* |
DE |
|
* The actual country of origin may differ depending on the delivery batch.
To confirm the specific country of origin, please contact your account manager.
|
| Harmonized System Code |
8536 3090 00
|
| ETIM |
EC000381
|
| Mounting method |
DIN rail (top hat rail) 35 mm |
| Lightning impulse current (10/350 µs) |
100 kA |
| Voltage protection level |
4 kV |
| Follow current extinguishing capability |
50 kA |
| Max. continuous voltage AC |
255 V |
| Nominal voltage AC |
230 V |
| Category type 1 |
Yes |
| Degree of protection (IP) |
IP20 |
Packing details
| Packing level 1 |
4013364109377, 4013364109377 |
Other Technical data
| Number of conductors (without earthing) |
3 |
| Construction size |
6 modular spacing |
| Max. conductor cross section solid (solid, stranded) |
50 mm² |
| Max. conductor cross section flexible (fine-strand) |
35 mm² |
| Specific energy (W/R) |
2500 kJ/Ohm |
| System configuration TN-C |
Yes |
Downloads
Description
Modular single-pole DEHNbloc H spark-gap-based lightning current arrester ( type 1 according to EN 61643-11).RADAX Flow spark gap technology with high follow current limitation. For protecting low-voltage consumer’s installations against surges and even direct lightning strikes. For installation in conformity with the lightning protection zone concept at the boundaries from 0A – 1.