Technical Information
| Item condition |
New |
| Manufacture name |
DS201 M C25 A30 110V Residual Current Circuit Breaker with Overcurrent Protection |
| Brand |
ABB
|
| Categories |
FI/LS-Schalter (RCBO)
|
| Harmonized System Code |
8536 3030 00
|
| ETIM |
EC000905
|
| Rated current |
25 A |
| Rated voltage |
230 V |
| Release characteristic |
C |
| Rated fault current |
0.03 A |
| Leakage current type |
A |
| Degree of protection (IP) |
IP2X |
| Number of protected poles |
1 |
| Ambient temperature during operating |
-25-55 °C |
| Number of poles (total) |
2 |
Packing details
| Packing level 1 |
8012542581116 |
| Packing level 2 |
8012542356813, 8012542581116 |
Other Technical data
| Voltage type |
AC |
| Built-in depth |
69 mm |
| Surge current capacity |
0 kA |
| Over voltage category |
3 |
| Pollution degree |
2 |
| Width in number of modular spacings |
2 |
| Frequency |
50/60 Hz |
| Concurrently switching neutral conductor |
Yes |
| Rated short-circuit breaking capacity according to IEC 60947-2 |
15 kA |
| With interlocking device |
No |
| Flush-mounted installation |
No |
| Anti-nuisance tripping version |
No |
| Disconnection characteristic |
Undelayed |
| Rated short-circuit breaking capacity according to EN 61009 |
10 kA |
Downloads
Description
The DS201 series is a 1P+N RCBO in two-modules width for the protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; protection against indirect contacts and additional protection against direct contacts. This particular range has the minimum operating voltage of test button of 110V