Technische Informationen
| Artikelzustand |
Neu |
| Herstellername |
Canalis - tap-off unit - 16A - 3L+N+PE - VDE power socket - with protection |
| Marke |
Schneider Electric
|
| Kategorien |
Abgangskästen
|
| Ursprungsland* |
FR |
|
* Das tatsächliche Ursprungsland kann je nach Liefercharge variieren.
Um das konkrete Ursprungsland zu bestätigen, wenden Sie sich bitte an Ihren Kundenbetreuer.
|
| Code des Harmonisierten Systems |
8536 9010 00
|
| ETIM |
EC000008
|
| Farbe |
Grau |
| Polzahl |
3 |
| Bemessungsspannung bei AC 50 Hz |
230-400 V |
| Bemessungsstrom bei AC 50 Hz |
16 A |
Verpackungsdetails
| Verpackungsstufe 1 |
3606480002342 |
Weitere technische Daten
| Breite |
53 mm |
| Höhe |
68 mm |
| RAL-Nummer |
7035 |
| Mit Einstellung |
Nein |
| Schutz |
Zylindersicherung |
| Anzahl Leiter (ohne Schutzleiter) |
2 |
| Phasenwahl |
Ja |
| Länge |
160 mm |
| Schutzart (IP) |
IP55 |
| Anzahl CEE-Steckdosen |
0 |
| Anzahl sonstiger Steckdosen |
1 |
| Abzweigart |
Steckdose |
| Steckdosentyp |
Schutzkontaktsteckdose (Typ F), 16 A |
| Anzahl NEMA-Steckdosen |
0 |
Downloads
Beschreibung
This is a tap-off unit with fuse protection for Canalis KBA, KBB and KDP busbar trunkings. Canalis KBA, KBB and KDP are designed for lighting and power socket distribution. The rated operational current is 16A at 35 ℃. The operational voltage is from 230VAC 50/60Hz to 240VAC 50/60Hz. Protection is ensured by a cylindrical fuse NF 8.5x31.5 (not supplied), with 16A gG type. Polarity is 3L+PE, with mobile studs. The power socket is a 2P+T with 10/16A and 250V electrical characteristics. It provides IP55 protection conforming to IEC 60529 standard, which guarantees trunking protection against splashes and dust. It provides IK06 protection conforming to IEC 62262 standard against external mechanical impacts. Canalis products are compliant with IEC/EN 61439-6 standard. It is non flame propagating as per the recommendations of IEC 60332-3 standard. All the insulating and plastic materials are halogen free and have enhanced fire withstand capabilities (IEC 60695-2).