Technical Information

Item condition New
Manufacture name Coordin. lightn. current arrester Type 1 DEHNbloc Maxi S 1-pole 255V
Brand Dehn
Categories Surge Protection Devices (SPD)
Country of origin* DE
* The actual country of origin may differ depending on the delivery batch. To confirm the specific country of origin, please contact your account manager.
Harmonized System Code 8536 3090 00
Mounting method Busbar
Lightning impulse current (10/350 µs) 25 kA
Voltage protection level 2.5 kV
Follow current extinguishing capability 50 kA
Max. continuous voltage AC 255 V
Nominal voltage AC 230 V
Category type 1 Yes

Packing details

Packing level 1 4013364106734, 4013364106734

Other Technical data

Number of conductors (without earthing) 1
Specific energy (W/R) 156.25 kJ/Ohm
System configuration TN Yes
System configuration TN-C Yes
System configuration TN-S Yes
System configuration TT Yes
System configuration TN-C-S Yes

Downloads

Description

Coordinated, single-pole spark-gap-based DEHNbloc Maxi S lightning current arrester (type 1 according to EN 61643-11) with integrated backup fuse for industrial busbar systems. High follow current extinguishing capability and follow current limitation due to RADAX Flow technology. For protecting low-voltage consumer´s installations against surges and even direct lightning strikes. For installation in conformity with the lightning protection zone concept at the boundaries from 0A – 1.