| Item condition | New |
| Manufacture name | Contactor DILM40-22 18.5kW 230VAC 2NO+2NC |
| Brand | EATON |
| Categories |
AC Power Contactors
|
| Country of origin* | RO |
| * The actual country of origin may differ depending on the delivery batch. To confirm the specific country of origin, please contact your account manager. | |
| Harmonized System Code | 8536 4900 00 |
| Rated operation power at AC-3, 400 V | 18.5 kW |
| Number of normally open contacts as main contact | 3 |
| Number of normally closed contacts as main contact | 0 |
| Rated operation current Ie at AC-3, 400 V | 40 A |
| Rated control supply voltage at AC 50 Hz | 230 V |
| Rated control supply voltage at AC 60 Hz | 240 V |
| Rated control supply voltage at DC | 0 V |
| Type of electrical connection of main circuit | Screw connection |
| Voltage type for actuating | AC |
| Packing level 1 | 4015082777982 |
| Modular version | No |
| Number of auxiliary contacts as normally open contact | 2 |
| Number of auxiliary contacts as normally closed contact | 2 |
| Rated operation current Ie at AC-1, 400 V | 60 A |
| Rated operation current Ie at AC-4, 400 V | 18 A |
| Rated operation power at AC-4, 400 V | 9 kW |
| Rated operation power NEMA | 22 kW |
Contactor, Application: Contactors for Motors, Complete devices up to 170 A, Utilization category: AC-1: Non-inductive or slightly inductive loads, resistance furnaces, NAC-3: Normal AC induction motors: starting, switch off during running, AC-4: Normal AC induction motors: starting, plugging, reversing, inching, Connection technique: Screw terminals, Notes: Also suitable for motors with efficiency class IE3., IE3-ready devices are identified by the logo on their packaging., Rated operational current AC-3 380 V 400 V: Ie= 40 A, Rated operational current AC-1 Conventional free air thermal current, 3 pole , 50 - 60 Hz Open at 40 °C: Ith =Ie= 60 A, enclosed: Ith= 45 A, Rated operational current AC-1 Conventional free air thermal current, 1 pole open: Ith= 125 A, enclosed: Ith= 112 A, Max. rating for three-phase motors, 50 - 60 Hz AC-3 220 V 230 V: P= 12.5 kW, 380 V 400 V: P= 18.5 kW, 660 V 690 V: P= 23 kW, Max. rating for three-phase motors, 50 - 60 Hz AC-4 220 V 230 V: P= 5 kW, 380 V 400 V: P= 9 kW, 660 V 690 V: P= 12 kW, Contacts N/O = Normally open: 2 N/O, Contacts N/C = Normally closed: 2 NC, Instructions: Contacts to EN 50 012., with mirror contact., Voltage AC/DC: AC operation