Technical Information
| Item condition |
New |
| Manufacture name |
Combined arrester type 1 + type 2 DEHNventil ZP f. three-phase TT a. T |
| Brand |
Dehn
|
| Categories |
Surge Protection Devices (SPD)
|
| Country of origin |
DE |
| Harmonized System Code |
8536 3090 00
|
| Lightning impulse current (10/350 µs) |
100 kA |
| Max. continuous voltage AC |
255 V |
| Nominal voltage AC |
230 V |
| Test class |
Type 1 + 2 |
| Voltage protection level L-N |
1.5 kV |
| Degree of protection (IP) |
IP30 |
| Voltage protection level N-PE |
1.5 kV |
Packing details
| Packing level 1 |
4013364105768, 4013364105768 |
Other Technical data
| Mounting method |
Busbar |
| Number of poles |
4 |
| Construction size |
3 modular spacing |
| Follow current extinguishing capability |
25 kA |
| Signalling at the device |
Optic |
| Specific energy (W/R) |
2500 kJ/Ohm |
| Energy-coordinated protection effect with regard to the terminal equipment |
Yes |
| System configuration TN-S |
Yes |
| System configuration TT |
Yes |
| Max. overcurrent protection device, parallel connection (fuse) |
315 A |
| Max. overcurrent protection device, series connection (fuse) |
315 A |
| Voltage switching spark gap technology |
Yes |
Downloads
Description
Multipole DEHNventil ZP type 1 and type 2 (according to EN 61643-11) combined lightning current and surge arrester for 40 mm busbar systems in the meter panel. Maximum system availability due to RADAX Flow current limitation. Capable of protecting terminal equipment. For protecting low-voltage consumer´s installations against surges and even direct lightning strikes. For installation in conformity with the lightning protection zone concept at the boundaries from 0A – 2.