Register to unlock your exclusive B2B prices and start shopping. Sign up now!
Circuit-breaker 63A 3p without bimetallic strip + withdrawable image 1
Circuit-breaker 63A 3p without bimetallic strip + withdrawable image 2
Circuit-breaker 63A 3p without bimetallic strip + withdrawable image 3
Circuit-breaker 63A 3p without bimetallic strip + withdrawable image 4
Circuit-breaker 63A 3p without bimetallic strip + withdrawable image 5
Circuit-breaker 63A 3p without bimetallic strip + withdrawable image 6
Circuit-breaker 63A 3p without bimetallic strip + withdrawable thumbnail 1
Circuit-breaker 63A 3p without bimetallic strip + withdrawable thumbnail 2
Circuit-breaker 63A 3p without bimetallic strip + withdrawable thumbnail 3
Circuit-breaker 63A 3p without bimetallic strip + withdrawable thumbnail 4
Circuit-breaker 63A 3p without bimetallic strip + withdrawable thumbnail 5
Circuit-breaker 63A 3p without bimetallic strip + withdrawable thumbnail 6

Circuit-breaker 63A 3p without bimetallic strip + withdrawable

In stock: No Vendor stock: No Minimal order quantity: 1
Price (excl. VAT):
192,83 €
This price is valid until 24.12.25
EAN: 4015081123322
MPN: 112792
Package: 1
Estimate delivery time at our warehouse (approx.): 4-6 weeks

Technical Information

Item condition New
Manufacture name Circuit-breaker 63A 3p without bimetallic strip + withdrawable
Brand EATON
Categories Power Circuit Breakers
Country of origin RO
Harmonized System Code 8536 2010 00
Rated permanent current Iu 63 A
Number of poles 3
Rated voltage 690 V
Degree of protection (IP) IP20
With switched-off indicator No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz 70 kA
Integrated earth fault protection No
Device construction Built-in device plug-in technique

Packing details

Packing level 1 4015081123322

Other Technical data

Number of auxiliary contacts as normally open contact 0
Number of auxiliary contacts as normally closed contact 0
With integrated under voltage release No
Overload release current setting 31.5-63 A
Number of auxiliary contacts as change-over contact 0
Position of connection for main current circuit Back side
Motor drive integrated No
Type of electrical connection of main circuit Other
Type of control element Rocker lever
Adjustment range short-term delayed short-circuit release 0 A
Adjustment range undelayed short-circuit release 8-14 A
Suitable for DIN rail (top hat rail) mounting No
Motor drive optional No
DIN rail (top hat rail) mounting optional No
Complete device with protection unit Yes

Description

Series NZM..-S circuit-breakers cover all application cases with just four compact sizes and are suitable for the IEC market. Modular function groups always make mounting flexible. With magnetic short-circuit release in connection with overload relay. With short-circuit release without overload trip. Notes: circuit-breakers fulfill all requirements of the switching category AC-3.