Technical Information
| Item condition |
New |
| Manufacture name |
Circuit-breaker 4p, 1600A, fixed |
| Brand |
EATON
|
| Categories |
Power Circuit Breakers
|
| Country of origin |
US |
| Harmonized System Code |
8536 2090 00
|
| Rated permanent current Iu |
1600 A |
| Number of poles |
4 |
| With switched-off indicator |
No |
| Integrated earth fault protection |
No |
Packing details
| Packing level 1 |
4015081211852 |
Other Technical data
| With integrated under voltage release |
No |
| Position of connection for main current circuit |
Back side |
| Motor drive integrated |
No |
| Suitable for DIN rail (top hat rail) mounting |
No |
| Motor drive optional |
No |
| DIN rail (top hat rail) mounting optional |
No |
| Complete device with protection unit |
No |
Downloads
Description
Circuit-breaker IZMX16 ( Air circuit-breakers/switch-disconnectors), 4 pole, Current Range: Up to 4000 A, Rated current = rated uninterrupted current( In = Iu): 1600 A, Rated ultimate short-circuit breaking capacity up to 440V/690V 42/42( Icu): 65 kA, Rated service short-circuit breaking capacity up to 440V/690V 42/42( Ics): 50 kA, Overload release, min.( Ir): 800 A, Overload release, max.( Ir): 1600 A, Installation type: Fixed, Standard/Approval: IEC, Protective function: Universal protection