Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Rated permanent current Iu
125 A
With integrated under voltage release
No
Number of poles
3
Overload release current setting
100-125 A
Number of auxiliary contacts as change-over contact
0
Rated voltage
440 V
Degree of protection (IP)
IP20
Position of connection for main current circuit
Front side
Motor drive integrated
No
Type of electrical connection of main circuit
Screw connection
Type of control element
Rocker lever
With switched-off indicator
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
25 kA
Adjustment range short-term delayed short-circuit release
0 A
Adjustment range undelayed short-circuit release
750-1250 A
Suitable for DIN rail (top hat rail) mounting
No
Integrated earth fault protection
No
Motor drive optional
Yes
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Yes
Complete device with protection unit
Yes
Packing details
Packing level 1
4015082590871
Description
Circuit-breaker, according to IEC/EN60947-2, with screw connections, screw fixing, Ui 690V, degree of protection IP20, finger proof according to VDE 0106 T. 100, adjustable overload release Ir = 0.8 – 1 × In, adjustable short-circuit release Ii = 6 – 10 × In and permanently set short-circuit release Ii as limitation, accessories: auxiliary contact modules, voltage release, remote operator, mounting accessories, terminal type, system housing, adapter