Technical Information
| Item condition |
New |
| Manufacture name |
BS fuse-link IEC gM A2 415VAC 250VDC 32M40A BTIA Offset Tag |
| Brand |
Mersen
|
| Categories |
HRC Fuses
|
| Country of origin* |
IN |
|
* The actual country of origin may differ depending on the delivery batch.
To confirm the specific country of origin, please contact your account manager.
|
| Harmonized System Code |
8536 1050 00
|
| Type of current |
AC/DC |
| Utilization category |
gM (motor protection) |
| Breaking capacity |
80 kA |
| Rated voltage AC |
415 V |
| Rated voltage DC |
250 V |
| Fuse construction type according to IEC 60269 |
A2 |
Packing details
| Packing level 1 |
3605340267557 |
Other Technical data
| Power loss at rated current |
2.4 W |
Description
The fuse complies with standard EN 60269-2 section II and standard BS 88 part 2. These fuses are designed for : “General purpose use” motor protection (gM type). This fuse range insures an excellent current limitation for all overloads on a large range of applications. Their size cannot allow exchange by other fuses of higher rating in their range. They are screwed into fuseholders or bolted directly onto busbars, or in fuse interruptors disconnectors.