Información técnica
| Estado del artículo |
Nuevo |
| Nombre del fabricante |
TF42-1.3B Thermal Overload Relay 1.0 ... 1.3 A |
| Marca |
ABB
|
| Categorías |
Relés térmicos de sobrecarga
|
| Código del Sistema Armonizado |
8536 4900 00
|
| ETIM |
EC000106
|
| Tipo de fijación |
Fijación directa |
| Clase de disparo |
CLASE 10 |
| Tipo de conexión eléctrica del circuito principal |
Conexión por tornillo |
| Tensión nominal de funcionamiento máx. Ue |
690 V |
| Rango de corriente ajustable |
1-1.3 A |
Detalles del embalaje
| Nivel de embalaje 1 |
4013614517099 |
| Nivel de embalaje 2 |
4013614517327 |
Otros datos técnicos
| Número de contactos auxiliares normalmente abiertos |
1 |
| Número de contactos auxiliares normalmente cerrados |
1 |
| Número de contactos auxiliares conmutados |
1 |
| Entrada para función de reinicio |
No |
| Función de reinicio automático |
Sí |
| Botón para función de reinicio |
Sí |
Descargas
Descripción
The TF42-B thermal overload relays are economic electromechanical protection devices for the main circuit, complying with the latest railway rolling stock standards and allowing installation in passengers or driver cabins for trains frequently operating tunnels or undergrounds.
They offer a reliable protection for motors in the event of overload or phase failure. The devices have trip
class 10.
The thermal overload relays are three pole relays with bimetal tripping elements. The motor current flows
through the bimetal tripping elements and heats them directly and indirectly. In case of an overload (over
current), the bimetal elements bent as a result of the heating. This leads to a release of the relay and a
change of the contacts switching position (95-96 / 97-98).
– Manual or automatic reset selectable
– Phase loss sensitive acc. to IEC/EN 60947-4-1
– TEST and STOP function – Trip indication on the front
– Temperature compensation
– Suitable for three- and single-phase applications
– designed in accordance to the applicable parts of IEC 60077 standard
– shocks and vibration withstand conforming to IEC 61373 (category 1, class B)
– usable according to European fire and smoke safety standard EN 45545-2