Información técnica
| Estado del artículo |
Nuevo |
| Nombre del fabricante |
RCCB with re-closer - RED - 4 poles - 25 A - class A - 30 mA |
| Marca |
Schneider Electric
|
| Categorías |
Interruptores diferenciales (RCCB)
|
| País de origen* |
PT |
|
* El país de origen real puede variar según el lote de suministro.
Para confirmar el país de origen concreto, póngase en contacto con su gestor de cuenta.
|
| Código del Sistema Armonizado |
8536 2010 90
|
| ETIM |
EC000003
|
| Tipo de tensión |
AC |
| Corriente nominal |
25 A |
| Tensión nominal |
400 V |
| Tensión nominal de aislamiento Ui |
500 V |
| Número de polos |
4 |
| Corriente nominal de cortocircuito |
30 A |
| Tipo de corriente residual |
A |
| Protección selectiva |
No |
| Capacidad de corte en cortocircuito (Icw) |
10 kA |
| Corriente de impulso |
0.25 kA |
| Desconexión con retardo breve |
No |
| Frecuencia |
50 Hz |
| Tensión nominal soportada a impulsos Uimp |
4 kV |
Detalles del embalaje
| Nivel de embalaje 1 |
3303430182641 |
| Nivel de embalaje 2 |
3303430182649 |
Otros datos técnicos
| Tipo de fijación |
Carril DIN |
| Profundidad de montaje |
44 mm |
| Grado de contaminación |
2 |
| Ancho en módulos |
7 |
| Protegido contra explosiones |
No |
| Grado de protección (IP) |
IP20 |
| Sección de conexión para conductores rígidos |
1.5-2.5 mm² |
| Sección de conexión para conductores multifilares |
1.5-2.5 mm² |
| Con dispositivo de bloqueo |
Sí |
| Temperatura ambiente durante el funcionamiento |
-5-40 °C |
| Admite equipamiento adicional |
Sí |
Descargas
Descripción
This Acti9 REDs is a modular residual current circuit breaker (RCCB) with recloser. It is a 4P circuit breaker with 25A In rated current, 30mA earth leakage sensitivity and A type protection class. This product protects against electrical shock by direct or indirect contact and fire hazards. It disconnects of on-load electric circuits already protected against overloads and short-circuits. It restarts automatically after insulation monitoring of the downstream circuit. It is only used on TT and TN-S earthing grounding systems. The Acti9 REDs and REDtest versions are dedicated to tertiary,industrial and infrastructure applications. This product is compliant with IEC/EN 61008-1 standard. The (Im/IΔm) rated breaking and making short circuit capacity is 630A. The (Inc/IΔc) conditional rated short circuit current is 6kA. It has a mechanical endurance going up to 4000 cycles. The Ue operational voltage is 400VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 4kV. The frequency is 50Hz. It is DIN rail mountable. The width in 9mm pitches is 14. The dimensions are (W) 125mm x (H) 98mm x (D) 79.5mm. The weight is 0.67kg. According to IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure. The operating temperature is from -5°C to 40°C. The storage temperature is from -20°C to 60°C.