Información técnica
| Estado del artículo |
Nuevo |
| Nombre del fabricante |
circuit breaker 3VA2 IEC Frame 160 breaking capacity class C Icu=110 kA @ 415 V 3-pole, line protection ETU330, LIG, In=25 A overload protection Ir=10 A ...25 A short-circuit protection Ii=1.5...12 3VA2125-7HM32-0BK0 |
| Marca |
Siemens
|
| Categorías |
Interruptores automáticos de potencia
|
| ETIM |
EC000228
|
Detalles del embalaje
| Nivel de embalaje 1 |
4042949322917 |
Descripción
circuit breaker 3VA2 IEC Frame 160 breaking capacity class C Icu=110 kA @ 415 V 3-pole, line protection ETU330, LIG, In=25 A overload protection Ir=10 A ...25 A short-circuit protection Ii=1.5...12 x In ground-fault protection Ig=0.2... 1 x In, tg=0.1/0.3s nut keeper kit undervoltage release (UVR) 24 V DC 1 auxiliary switch HQ 1 trip alarm switch HQ 1 electrical alarm switch